CD-10i ceiling panel
A
B
Code
31 103
31 104
31 105
Specifications
Insulating
Sur.
material
B
H
mm
mm
1200
45
1200
45
1200
45
EPS 200
2.40
EPS 200
1.20
EPS 200
0.60
13
2000
13
1000
13
500
Weight
A
m
2
kg/m
2
mm
CD-10i prefabricated radiant panel for suspended ceilings, made up of 15 mm
plasterboard cladding combined with a 30 mm EPS 200 polystyrene panel in order
to increase thermal efficiency towards the rooms to be heated. Inside the plaster-
board sheet there is a type II PE-RT 10 x 1,3 mm, 5 layer pipe, the central layer be-
ing an EVOH oxygen barrier. The layout of the circuit spaced at 50 mm, is indicated
on the face of the plasterboard sheet.
Use
Prefabricated panel for creating dry radiant ceiling systems.
This panel is designed to be suspended from the supporting structure of a double
framework suspended ceiling, especially hanging on 50x27 mm channel sections
of the secondary framework, spaced at 50 cm. Minimum thickness between the
rough and finished ceiling 15 cm (18 cm recommended).
These panels' modularity makes it possible to achieve percentage coverage up
to 65 -75% of the area available. The only type of cladding that can be used with
this type of panel, is what makes up the panel itself, that is a smooth clad sheet of
gypsum board (
=0,21 W/m·K).
The hydraulic connections between the panels must be made using the reverse
return system (Tichelmann), which ensures limited pressure loss, and the same
supply temperature.
Passive infill panel
Code
Insulating
material
31 901
EPS 200
Specifications
Sur.
Weight
A
B
H
m
2
kg/m
2
mm
mm
mm
2.40
13
2000
1200
45
A
B
Prefabricated panel for suspended ceilings or wall lining, made up of 15 mm
plasterboard cladding, combined with a 30 mm EPS 200 polystyrene panel.
Use
These are used to fill in spaces in the suspended ceiling not occupied by the CD-
10i radiant panels.
42
Ceiling and wall radiant system – Product guide
Tel. +39 0425 75 88 11