A

B

Code

31 203

Specifications

Insulating

material

EPS 200

Sur.

Weight

m

2

kg/m

2

1.20

13

A

B

H

mm

mm

mm

2000

600

45

WD-10i wall panel

Wd-10i prefabricated radiant panel for wall lining, made up of 15 mm plasterboard

cladding combined with a 30mm EPS 200 polystyrene panel in order to increase

thermal efficiency towards the rooms to be heated. Inside the plasterboard sheet

there is a type II PE-RT 10 x 1,3 mm, 5 layer pipe, the central layer being an EVOH

oxygen barrier. The layout of the circuit spaced at 50 mm, is indicated on the face

of the plasterboard sheet.

Use

Prefabricated panel for creating radiant drywall systems.

This panel is made to be screwed to the supporting structure of a wall lining, es-

pecially screwed to channel sections used to form vertical stud spaced at 60 cm.

Minimum thickness between the rough and finished wall 10 cm.

The only type of cladding that can be used with this type of panel, is what makes

up the panel itself, that is a smooth clad sheet of gypsum board (

λ

=0,21 W/m·K).

The hydraulic connections between the panels must be made using the reverse

return system (Tichelmann), which ensures limited pressure loss, and the same

supply temperature.

46

Ceiling and wall radiant system – Product guide

Tel. +39 0425 75 88 11

A

B

Passive infill panel

Code

Insulating

material

31 901

EPS 200

Specifications

Sur.

Weight

m

2

kg/m

2

2.40

13

A

B

H

mm

mm

mm

2000

1200

45

Prefabricated panel for suspended ceilings or wall lining, made up of 15 mm plas-

terboard cladding, combined with a 30 mm EPS 200 polystyrene panel.

Use

These panels are used to fill in spaces in the suspended ceiling not occupied by

the WD- 10i radiant panels.