Rules for dimensioning / constructing WW-10 systems

built on site

1. Maximum active area of the radiant circuit 11,00 sq.m.

2. Maximum active area of the radiant panel 1,875 sq.m.

equivalent to 25 LM of piping (20 recommended).

3. In order to optimise the system's performance, we recom-

mend connecting the panels using the Tichelmann system

(with reverse return), and therefore the length of pipe for

each individual panel must not differ by more than 10% for

all the panels that make up a specific circuit.

4. The panel can be rectangular or L-shaped.

5. Clip rails at approx 35 cm spacing (3.5 m/sq.m).

6. One support bracket for each curve in the panel (13 pcs/m

of width of active panel).

7. To anchor the clip rails, use hot glue or screws suitable for

the base.