Rules for dimensioning / constructing WW-10 systems
built on site
1. Maximum active area of the radiant circuit 14,00 sq.m.
2. Maximum active area of the radiant panel 2,25 sq.m.
equivalent to 30 ml of piping (25 recommended).
3. In order to optimise the system's performance, we
recommend connecting the panels using the Tichelmann
system (with reverse return), and therefore the length of
pipe for each individual panel must not differ by more than
10% for all the panels that make up a specific circuit.
4. The panel can be rectangular or L-shaped.
5. Clip rails spaced at approx 30 cm (4 m/sq.m).
6. One support bracket for each curve in the panel (13 pcs/m
of width of active panels).
7. To anchor the clip rails, use hot glue or screws suitable for
the base.
Fig. 1 Example of distribution for WW-10 ceiling panels
www.wavin.it
Ceiling and wall radiant system – Product guide
25