Installation - Hydraulic connections

In order to optimise the system's performance, we recommend

connecting the panels using the Tichelmann system (with

reverse return), thereby facilitating self-balancing of each

individual outgoing circuit of the manifold.

The sum of the lengths of the panels in series must not differ

from the lengths of the individual panels by more than 10%

within the same circuit.

* Mixed press-fit, push-fit Tee 10 -16 -10 mm

** Mixed press-fit, push-fit coupling 16 - 10 mm